7.1.4 Signals
PID-6815-INPUTSIGNALS v3
Table 43: ZMFPDIS Input signals
Name
Type Default Description
I3P GROUP
SIGNAL
- Group signal for current input
U3P GROUP
SIGNAL
- Group signal for voltage input
BLOCK BOOLEAN 0 Blocks and resets timers and outputs of entire
function
VTSZ BOOLEAN 0 Blocks and resets timers and outputs of entire
function
BLKZ1 BOOLEAN 0 Blocks and resets zone 1 timers and outputs
BLKZ2 BOOLEAN 0 Blocks and resets zone 2 timers and outputs
BLKZ3 BOOLEAN 0 Blocks and resets zone 3 timers and outputs
BLKZ4 BOOLEAN 0 Blocks and resets zone 4 timers and outputs
BLKZ5 BOOLEAN 0 Blocks and resets zone 5 timers and outputs
BLKZRV BOOLEAN 0 Blocks and resets reverse zone timers and
outputs
BLKTRZ1 BOOLEAN 0 Blocks and resets zone 1 timers and trip outputs
BLKTRZ2 BOOLEAN 0 Blocks and resets zone 2 timers and trip outputs
BLKTRZ3 BOOLEAN 0 Blocks and resets zone 3 timers and trip outputs
BLKTRZ4 BOOLEAN 0 Blocks and resets zone 4 timers and trip outputs
BLKTRZ5 BOOLEAN 0 Blocks and resets zone 5 timers and trip outputs
BLKTRZRV BOOLEAN 0 Blocks and resets reverse zone timers and trip
outputs
EXTNST BOOLEAN 0 External start of zone timers
RELCNDZ1 INTEGER 127 Release word for the measuring loops of zone 1
RELCNDZ2 INTEGER 127 Release word for the measuring loops of zone 2
RELCNDZ3 INTEGER 127 Release word for the measuring loops of zone 3
RELCNDZ4 INTEGER 127 Release word for the measuring loops of zone 4
RELCNDZ5 INTEGER 127 Release word for the measuring loops of zone 5
RELCNDZRV INTEGER 127 Release word for the measuring loops of zone RV
PID-7066-OUTPUTSIGNALS v1
Table 44: ZMFPDIS Output signals
Name
Type Description
TRIP BOOLEAN Trip in any phase or phases from any zone or
zones
TRZ1 BOOLEAN Trip in any phase or phases from zone 1 -
forward direction
TRL1Z1 BOOLEAN Trip in phase L1 from zone 1 - forward direction
TRL2Z1 BOOLEAN Trip in phase L2 from zone 1 - forward direction
Table continues on next page
1MRK 505 394-UEN A Section 7
Impedance protection
Line differential protection RED650 2.2 IEC 113
Technical manual