ABB RED650 - Technical Data

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Direction
Element
4 step over current
element
One element for each
step
Harmonic
Restraint
Mode
Selection
earthFaultDirection
harmRestrBlock
enableDir
enableStep
1-4
DirectionalMode
1-4
TRIP
Element
enableDir
angleValid
Directional Check
operatingCurrent
SwitchOnToFault
start step 2, 3 and 4
signal to
communication
scheme
TRIP
3U0
3I0
Blocking at parallel
transformers
1
CB
pos
or cmd
Element
3I0
DirMode
DirMode
INPol
IEC06000376-2-en.vsd
I3PDIR
IEC06000376 V3 EN-US
Figure 90: Functional overview of EF4PTOC
8.4.8 Technical data
IP11455-1 v1
M15223-1 v17
Table 89: EF4PTOC technical data
Function
Range or value Accuracy
Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio > 95% at (10-2500)% of IBase -
Relay characteristic angle
(RCA)
(-180 to 180) degrees ±2.0 degrees
Operate current for directional release (1–100)% of IBase For RCA ±60
degrees:
±2.5% of I
r
at I ≤ I
r
±2.5% of I at I > I
r
Independent time delay at 0 to 2 x I
set
, step
1-4
(0.000-60.000) s ±0.2% or ±35 ms
whichever is
greater
Minimum operate time for inverse curves,
step 1-4
(0.000 - 60.000) s ±0.2% or ±35 ms
whichever is
greater
Table continues on next page
1MRK 505 394-UEN A Section 8
Current protection
Line differential protection RED650 2.2 IEC 203
Technical manual