5.3.3 Signals
PID-4114-INPUTSIGNALS v5
Table 23: LEDGEN Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Input to block the operation of the LEDs
RESET BOOLEAN 0 Input to acknowledge/reset the indication LEDs
PID-4114-OUTPUTSIGNALS v5
Table 24: LEDGEN Output signals
Name Type Description
NEWIND BOOLEAN New indication signal if any LED indication input
is set
ACK BOOLEAN A pulse is provided when the LEDs are
acknowledged
PID-1697-INPUTSIGNALS v18
Table 25: GRP1_LED1 Input signals
Name Type Default Description
HM1L01R BOOLEAN 0 Red indication of LED1, local HMI alarm group 1
HM1L01Y BOOLEAN 0 Yellow indication of LED1, local HMI alarm group
1
HM1L01G BOOLEAN 0 Green indication of LED1, local HMI alarm group
1
5.3.4 Settings
PID-4114-SETTINGS v6
Table 26: LEDGEN Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.1 - 100.0 s 0.1 1.0 Maximum time for the definition of a
disturbance
1MRK 505 394-UEN A Section 5
Local Human-Machine-Interface LHMI
Line differential protection RED650 2.2 IEC 63
Technical manual