EasyManua.ls Logo

ABB RED650 - Inverse Characteristics

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25.3 Inverse characteristics
IP15797-1 v2
M12388-1 v21
Table 660: ANSI Inverse time characteristics
Function
Range or value Accuracy
Operating characteristic:
( )
1
P
A
t B k tDef
I
æ ö
ç ÷
= + × +
ç ÷
ç - ÷
è ø
EQUATION1249-SMALL V2 EN-US
Reset characteristic:
( )
2
1
= ×
-
t
r
t k
I
EQUATION1250-SMALL V1 EN-US
I = I
measured
/I
set
0.10 ≤ k ≤ 3.00
1.5 x I
set
≤ I ≤ 20 x I
set
ANSI/IEEE C37.112 ,
±2.0% or ±40 ms
whichever is greater
ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 ,
tr=29.1
ANSI Very inverse A=19.61, B=0.491, P=2.0 ,
tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02,
tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02,
tr=4.85
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0,
tr=30
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse A=0.086, B=0.185, P=0.02,
tr=4.6
1MRK 505 394-UEN A Section 25
Inverse time characteristics
Line differential protection RED650 2.2 IEC 877
Technical manual

Table of Contents

Other manuals for ABB RED650

Related product manuals