Name Type Description
COUNT3P3 INTEGER Number of three-phase shot 3 reclosings
COUNT3P4 INTEGER Number of three-phase shot 4 reclosings
COUNT3P5 INTEGER Number of three-phase shot 5 reclosings
COUNTAR INTEGER Number of total reclosing shots
MODE INTEGER Integer output for reclosing mode
ABORTED BOOLEAN General abort
SYNCFAIL BOOLEAN AR sequence is aborted by synchrocheck
conditions not fulfilled
INHIBOUT BOOLEAN AR sequence is aborted via INHIBIT input
12.2.5 Settings
PID-6796-SETTINGS v2
Table 173: SMBRREC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
ExternalCtrl Off
On
- - Off To be set On if AR is to be used with
external control
ARMode 3 phase
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
-
- 1/2/3ph AR mode selection
t1 1Ph 0.000 - 120.000 s 0.001 1.000 Dead time for shot 1, single-phase
reclosing
t1 3Ph 0.000 - 120.000 s 0.001 6.000 Dead time for shot 1, delayed three-
phase reclosing with synchrocheck
conditions
t1 3PhHS
0.000 - 120.000 s 0.001 0.400 Dead time for shot 1, high speed three-
phase reclosing
tReclaim 0.00 - 6000.00 s 0.01 60.00 Reclaim time
tSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for fulfilled
synchrocheck conditions
tLongStartInh 0.000 - 60.000 s 0.001 0.200 Maximum allowed start pulse duration
tPulse 0.000 - 60.000 s 0.001 0.200 Circuit breaker closing pulse duration
tCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that circuit breaker must
be closed before new sequence is
allowed
tUnsucCl
0.00 - 6000.00 s 0.01 30.00 Maximun wait time for circuit breaker
closing before indicating unsuccessful
Table continues on next page
Section 12 1MRK 505 394-UEN A
Control
324 Line differential protection RED650 2.2 IEC
Technical manual

Table of Contents