22.5.5  Type tests according to standard
IP16288-1 v1
M16706-1 v9
Table 655: Electromagnetic compatibility
Test Type test values Reference standards
1 MHz burst disturbance 2.5 kV IEC 60255-26
100 kHz slow damped
oscillatory wave immunity
test
2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test,
100 kHz
2-4 kV IEC 61000-4-12, Class IV
Surge withstand capability
test
2.5 kV, oscillatory
4.0 kV, fast transient
IEEE/ANSI C37.90.1
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-26
IEC 61000-4-2, Class IV
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.1
Fast transient disturbance
4 kV
(SFP galvanic RJ45: 2kV)
IEC 60255-26, Zone A
Surge immunity test
2-
4 kV, 1.2/50 ms
high energy
IEC 60255-26, Zone A
Power frequency immunity
test
150-
300 V, 50 Hz IEC 60255-26, Zone A
Conducted common mode
immunity test
15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic
field test
1000 A/m, 3 s
100 A/m, cont.
IEC 61000-4-8, Class V
Pulse magnetic field
immunity test
1000 A/m IEC 61000–4–9, Class V
Damped oscillatory magnetic
field test
100 A/m IEC 61000-4-10, Class V
Radiated electromagnetic
field disturbance
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-26
Radiated electromagnetic
field disturbance
20 V/m
80-
1000 MHz
IEEE/ANSI C37.90.2
Conducted electromagnetic
field disturbance
10 V, 0.15-80 MHz IEC 60255-26
Radiated emission 30-
5000 MHz IEC 60255-26
Radiated emission 30-
5000 MHz IEEE/ANSI C63.4, FCC
Conducted emission 0.15-30 MHz IEC 60255-26
Table 656: Insulation
Test Type test values Reference standard
Dielectric test
2.0 kV AC, 1 min.
(SFP galvanic RJ45: 1.0 
kV, 1 min.)
IEC 60255-27
ANSI C37.90
IEEE 802.3-2015, 
Environment A
Impulse voltage test
5 kV, 1.2/50 
ms, 0.5 J
Insulation resistance
> 100 MW
 at 500 VDC
Section 22 1MRK 505 394-UEN A
IED hardware
862 Line differential protection RED650 2.2 IEC
Technical manual