8.7.8 Technical data
M13279-1 v10
Table 114: CCPDSC technical data
Function
Range or value Accuracy
Operate current (0–100)% of
IBase
±1.0% of I
r
Independent time delay
between trip condition and trip
signal
(0.000-60.000) s
±0.2% or ± 30 ms whichever
is greater
1MRK 505 394-UEN A Section 8
Current protection
Line differential protection RED650 2.2 IEC 225