14.7.7 Reset-set with memory function block RSMEMORY
GUID-9C93669F-078B-49EA-85B8-C4BB6A434734 v1
GUID-4C804DEA-3C83-4C20-82C6-BAD03BD48242 v4
The Reset-set with memory function block (RSMEMORY) is a flip-flop with
memory that can reset or set an output from two inputs respectively. Each
RSMEMORY function block has two outputs, where one is inverted. The memory
setting controls if, after a power interruption, the flip-flop resets or returns to the
state it had before the power interruption. For a Reset-Set flip-flop, RESET input
has higher priority over SET input.
Table 293: Truth table for RSMEMORY function block
RESET SET OUT NOUT
0 0 Last
value
Inverted last
value
0 1 1 0
1 0 0 1
1 1 0 1
14.7.7.1 Function block
GUID-50D5A4C0-59BF-44DE-86AC-47640ACD35A7 v3
RSMEMORY
SET
RESET
OUT
NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN-US
Figure 236: RSMEMORY function block
14.7.7.2 Signals
PID-3811-INPUTSIGNALS v5
Table 294: RSMEMORY Input signals
Name
Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
PID-3811-OUTPUTSIGNALS v5
Table 295: RSMEMORY Output signals
Name
Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
Section 14 1MRK 505 394-UEN A