14.7.8.2  Signals
PID-3813-INPUTSIGNALS v5
Table 299: SRMEMORY Input signals
Name
Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
PID-3813-OUTPUTSIGNALS v5
Table 300: SRMEMORY Output signals
Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
14.7.8.3  Settings
PID-3813-SETTINGS v5
Table 301: SRMEMORY Group settings (basic)
Name
Values (Range) Unit Step Default Description
Memory Off
On
- - On Operating mode of the memory function
14.7.8.4  Technical data
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v1
Table 302: Number of SRMEMORY instances
Logic block
  Quantity with cycle time  
 
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
14.7.9  Settable timer function block TIMERSET
IP11022-1 v2
M11494-3 v3
The Settable timer function block (TIMERSET) timer has two outputs for the delay
of the input signal at drop-out and at pick-up. The timer has a settable time delay. It
also has an Operation setting On and Off that controls the operation of the timer.
Section 14 1MRK 505 394-UEN A
Logic
468 Line differential protection RED650 2.2 IEC
Technical manual