EasyManua.ls Logo

ABB RED650 - Function Block; Signals

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.1.3 Function block
M12638-3 v7
SMPPTRC
BLOCK
BLKLKOUT
TRIN
TRINL1
TRINL2
TRINL3
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
S ETLKOUT
RSTLKOUT
STDI R
TRIP
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOU T
STAR T
STL1
STL2
STL3
STN
FW
REV
IEC05000707-4-en.vsdx
IEC05000707 V4 EN-US
Figure 214: SMPPTRC function block
14.1.4 Signals
GUID-2918ECA6-4D98-493F-A33C-2D33DE64AE3B v1
Table 249: SMPPTRC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKLKOUT BOOLEAN 0 Blocks circuit breaker lockout output (CLLKOUT)
TRIN BOOLEAN 0 Trip all phases
TRINL1 BOOLEAN 0 Trip phase L1
TRINL2 BOOLEAN 0 Trip phase L2
TRINL3 BOOLEAN 0 Trip phase L3
PSL1 BOOLEAN 0 Functional input for phase selection in phase L1
PSL2 BOOLEAN 0 Functional input for phase selection in phase L2
PSL3 BOOLEAN 0 Functional input for phase selection in phase L3
1PTRZ BOOLEAN 0 Input for phase selective carrier aided trip
1PTREF BOOLEAN 0 Input for phase selective earth fault trip
P3PTR BOOLEAN 0 Prepare all tripping to be three-phase
SETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout
function
RSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout
function
STDIR INTEGER 0 General start direction input
Section 14 1MRK 505 394-UEN A
Logic
432 Line differential protection RED650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB RED650