PID-1697-SETTINGS v18
Table 27: GRP1_LED1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
SequenceType Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
-
- Follow-S Sequence type for LED 1, local HMI
alarm group 1
LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm
group 1 is off
LabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm
group 1 is red
LabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm
group 1 is green
5.4 LCD part for HMI function keys control module
GUID-EECAE7FA-7078-472C-A429-F7607DB884EB v2
5.4.1 Identification
GUID-E6611022-5EA3-420D-ADCD-9D1E7604EFEB v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
LCD part for HMI Function Keys
Control module
FNKEYMD1 -
FNKEYMD5
- -
5.4.2 Function block
GUID-A803A728-5CFC-4606-98E4-793E873B99D4 v3
FNKEYMD1
^LEDCTL1 ^FKEYOUT1
IEC09000327 V1 EN-US
Figure 6: FNKEYMD1 function block
Only the function block for the first button is shown above. There is a similar block
for every function key button.
5.4.3 Signals
PID-1657-INPUTSIGNALS v18
Table 28: FNKEYMD1 Input signals
Name
Type Default Description
LEDCTL1 BOOLEAN 0 LED control input for function key