22.2.2.3 Technical data
SEMOD55319-1 v1
SEMOD55310-2 v11
Table 614: SFP - Optical ethernet port
Quantity
Rated value
Number of channels 4 single or 2 redundant can be used for single or
redundant communication using any protocol
Standard IEEE 802.3u 100BASE-FX
Type of fiber
62.5/125 mm multimode fibre
Wave length 1310 nm, Class 1 laser safety
Optical connector Type LC
Communication speed Fast Ethernet 100 Mbit/s
Table 615: SFP - Galvanic RJ45
Quantity Rated value
Number of
channels
Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
Standard IEEE 802.3u 100BASE-TX
Type of cable Cat5e FTP
Connector Type RJ45
Communication
Speed
Fast Ethernet 100 Mbit/s
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2
Table 616: NUM: Communication ports
NUM
4 Ethernet ports
1 Basic, 3 Optional
Ethernet connection type SFP Optical LC or Galvanic RJ45
Carrier modules supported LDCM
22.2.3 Power supply module (PSM)
IP15594-1 v1
22.2.3.1 Introduction
M11595-3 v6
The power supply module is used to provide the correct internal voltages and full
isolation between the IED and the battery system. An internal fail alarm output is
available.
Alternative connectors of Ring lug or Compression type can be ordered.
1MRK 505 394-UEN A Section 22
IED hardware
Line differential protection RED650 2.2 IEC 813
Technical manual

Table of Contents

Other manuals for ABB RED650

Related product manuals