EasyManua.ls Logo

ABB RED650 - Setting Parameters for Binary Input Modules; Setting Parameters for Binary Input;Output Module

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.1.3.1 Setting parameters for binary input modules
PID-3473-SETTINGS v2
Table 19: BIM Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit
4.1.3.2 Setting parameters for binary input/output module
PID-4050-SETTINGS v2
Table 20: IOMIN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Binary input/output module in operation
(On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit
Section 4 1MRK 505 394-UEN A
Binary input and output modules
60 Line differential protection RED650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB RED650

Related product manuals