PID-6966-OUTPUTSIGNALS v2
Table 420: L4UFCNT Output signals
Name Type Description
ERROR BOOLEAN Error indication on counter limit and/or initial
value settings
OVERFLOW BOOLEAN Overflow indication on count of greater than
MaxValue
LIMIT1 BOOLEAN Counted value is larger than or equal to
CounterLimit1
LIMIT2 BOOLEAN Counted value is larger than or equal to
CounterLimit2
LIMIT3 BOOLEAN Counted value is larger than or equal to
CounterLimit3
LIMIT4 BOOLEAN Counted value is larger than or equal to
CounterLimit4
VALUE INTEGER Counted value
15.10.6 Settings
PID-6966-SETTINGS v2
Table 421: L4UFCNT Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
CountType Positive edge
Negative edge
Both edges
-
- Positive edge Select counting on positive and/or
negative flanks
CounterLimit1 1 - 65535 - 1 100 Value of the first limit
CounterLimit2 1 - 65535 - 1 200 Value of the second limit
CounterLimit3 1 - 65535 - 1 300 Value of the third limit
CounterLimit4 1 - 65535 - 1 400 Value of the fourth limit
MaxValue 1 - 65535 - 1 500 Maximum count value
OnMaxValue Stop
Rollover Steady
Rollover Pulsed
-
- Stop Select if counter stops or rolls over after
reaching maxValue with steady or
pulsed overflow flag
InitialValue
0 - 65535 - 1 0 Initial count value after reset of the
function
15.10.7 Monitored data
PID-6966-MONITOREDDATA v2
Table 422: L4UFCNT Monitored data
Name
Type Values (Range) Unit Description
VALUE INTEGER - - Counted value