applicable to very long time accumulation (≤99999.9 hours)
output ACC_HOUR presents accumulated value in hours and ACC_DAY
presents accumulated value in days
accumulated value is retained in a non-volatile memory
any retained value is used as initiation value for the integration following
by a restart
RESET: Reset of the accumulated value. Consequently all other outputs are
also reset
independent of the input IN value
reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input IN is
high during the reset.
reset can be made by activation of input RESET or from LHMI or with
IEC 61850 command
ADDTIME: Manually add time to the currently accumulated time
the amount of time to be added is defined by a setting tAddToTime
time is added through activation of input ADDTIME or from LHMI or
with IEC 61850 command
BLOCK: Freeze the accumulation and block/reset the other outputs
independent of the input IN value
BLOCK request overrides RESETrequest
Monitor and report the conditions of limit transgression
overflow if output ACC_HOUR > 99 999.9 hours
alarm if output ACC_HOUR > tAlarm
warning if output ACC_HOUR > tWarning
The ACC_HOURoutput represents the accumulated time in hours and the
ACC_DAY output represents the accumulated time in days.
tAlarm and tWarning are user settable time limit parameters in hours. They are also
independent of each other, that is, there is no check if tAlarm > tWarning.
tAddToTime is a user settable time parameter in hours.
tAlarm, tWarning and tAddToTime are possible to be defined with a resolution of
0.1 hours (6 minutes).
The limit for the overflow supervision is fixed at 99999.9 hours. The outputs will
reset and the accumulated time will reset and start from zero if an overflow occurs.
15.11.6.1 Operation accuracy
GUID-B6FBEFD7-17C8-41C6-B5D5-32E1205E6752 v1
The accuracy of TEILGAPC depends on essentially two factors
Section 15 1MRK 505 394-UEN A
Monitoring
606 Line differential protection RED650 2.2 IEC
Technical manual