18.8.7 IED status for IEC 60870-5-103 I103IED
18.8.7.1 Functionality
GUID-52AC7D0F-33C5-46FC-983E-5CB4B3517D88 v1
I103IED is a function block with defined IED functions in monitor direction. This
block uses parameter as FunctionType, and information number parameter is
defined for each input signal.
18.8.7.2 Identification
GUID-5EEBE11C-C8E3-4A8A-814F-840E137DB5B5 v1
Function description Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED status for IEC 60870-5-103 I103IED - -
18.8.7.3 Function block
GUID-421D5C37-27A5-476A-A7D9-40E70AFDFDC8 v1
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN-US
Figure 342: I103IED function block
18.8.7.4 Signals
PID-3975-INPUTSIGNALS v5
Table 510: I103IED Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
19_LEDRS BOOLEAN 0 Information number 19, reset LEDs
21_TESTM BOOLEAN 0 Information number 21, test mode is active
22_SETCH BOOLEAN 0 Information number 22, setting changed
23_GRP1 BOOLEAN 0 Information number 23, setting group 1 is active
24_GRP2 BOOLEAN 0 Information number 24, setting group 2 is active
25_GRP3 BOOLEAN 0 Information number 25, setting group 3 is active
26_GRP4 BOOLEAN 0 Information number 26, setting group 4 is active
1MRK 505 394-UEN A Section 18