Name Type Default Description
ZONESTEP BOOLEAN 0 Coordinate local AR with down stream devices
TR2P BOOLEAN 0 Two phase trip occurred
TR3P BOOLEAN 0 Three phase trip occurred
THOLHOLD BOOLEAN 0 Hold AR in wait state
CBREADY BOOLEAN 0 Circuit breaker is ready
CBCLOSED BOOLEAN 0 Circuit breaker status
PLCLOST BOOLEAN 0 Power line carrier or other form of permissive
signal is lost
SYNC BOOLEAN 0 Synchrocheck conditions are fulfilled
WAIT BOOLEAN 0 Wait for master
RSTCOUNT BOOLEAN 0 Reset counters
MODEINT INTEGER 0 Integer input used to set reclosing mode
(alternative to setting)
PID-6796-OUTPUTSIGNALS v2
Table 172: SMBRREC Output signals
Name Type Description
BLOCKED BOOLEAN AR is blocked
SETON BOOLEAN AR is operative
READY BOOLEAN AR is ready for a new sequence
ACTIVE BOOLEAN Reclosing sequence in progress
SUCCL BOOLEAN Reclosing is successful
UNSUCCL BOOLEAN Reclosing is unsuccessful
INPROGR BOOLEAN Reclosing in progress, inactive during reclaim
time
1PT1 BOOLEAN Single-phase reclosing is in progress for shot 1
2PT1 BOOLEAN Two-phase reclosing is in progress for shot 1
3PT1 BOOLEAN Three-phase reclosing is in progress for shot 1
3PT2 BOOLEAN Three-phase reclosing is in progress for shot 2
3PT3 BOOLEAN Three-phase reclosing is in progress for shot 3
3PT4 BOOLEAN Three-phase reclosing is in progress for shot 4
3PT5 BOOLEAN Three-phase reclosing is in progress for shot 5
PERMIT1P BOOLEAN Single-phase trip is permitted
PREP3P BOOLEAN Three-phase trip is prepared
CLOSECB BOOLEAN Close command for circuit breaker
WFMASTER BOOLEAN Wait signal to slave issued by master for
sequential reclosing
COUNT1P INTEGER Number of single-phase reclosing shots
COUNT2P INTEGER Number of two-phase reclosing shots
COUNT3P1 INTEGER Number of three-phase shot 1 reclosings
COUNT3P2 INTEGER Number of three-phase shot 2 reclosings
Table continues on next page
1MRK 505 394-UEN A Section 12
Control
Line differential protection RED650 2.2 IEC 323
Technical manual