Table 107: Dependencies between parameters RetripMode and FunctionMode
RetripMode FunctionMode
Description
Retrip Off
N/A The re-trip function is not
activated.
CB Pos Check Current
The re-trip will follow the
function mode.
Contact
Current/Contact
No CBPos Check Current
The re-trip is done
unconditionally.
Contact
Current/Contact
The start signal can be an internal or external protection trip signal. This signal will
start the back-up trip timer. The function detects the successful breaker opening,
either by detection of low current through RMS evaluation and a special adapted
current algorithm or by open contact indication. The special algorithm enables a
very fast detection of successful breaker opening, that is, fast resetting of the
current measurement. If the current and/or contact detection has not detected
breaker opening before the back-up timer has run its time a back-up trip is initiated.
Further the following possibilities are available:
The minimum length of the re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the
back-up trip pulse 2 will however sustain as long as there is an indication of
closed breaker.
In the current detection it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out
of 4 where it is sufficient to detect failure to open (high current) in one pole or
high residual current and 2 out of 4 where at least two current (phase current
and/or residual current) shall be high for breaker failure detection.
The current detection level for the residual current can be set different from the
setting of phase current detection.
It is possible to have different back-up time delays for single-phase faults and
for multi-phase faults.
The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
It is possible to have instantaneous back-up trip function if a signal is high if
the circuit breaker is incapable to clear faults, for example at low gas pressure.