EasyManua.ls Logo

ABB RED650 - Page 253

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
where:
Un> Set value for step 1 and step 2
U Measured voltage
The type B curve is described as:
2.0
480
0.035
32 0.5
n
n
k
t
UU
U






IECEQUATION2423 V2 EN-US (Equation 44)
The type C curve is described as:
3.0
480
0.035
32 0.5
n
n
k
t
U U
U
×
= +
æ ö
- >
× -
ç ÷
>
è ø
IECEQUATION2425 V1 EN-US (Equation 45)
The customer programmable curve is defined by the below equation, where A, B,
C, D, k and p are settings:
p
n
n
k A
t D
U U
B C
U
×
= +
æ ö
- >
× -
ç ÷
>
è ø
EQUATION1439 V2 EN-US
(Equation 46)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval Un> up
to Un> · (1.0 + CrvSatn/100) the used voltage will be: Un> · (1.0 + CrvSatn/100).
If the programmable curve is used this parameter must be calculated so that:
0
100
CrvSatn
B C× - >
EQUATION1435 V1 EN-US (Equation 47)
The highest phase (or phase-to-phase) voltage is always used for the inverse time
delay integration, see figure 112. The details of the different inverse time
characteristics are shown in section "Inverse characteristics".
1MRK 505 394-UEN A Section 9
Voltage protection
Line differential protection RED650 2.2 IEC 247
Technical manual

Table of Contents

Other manuals for ABB RED650

Related product manuals