IEC16000153-1-en.vsdx
TRSOTF
Operation
AND
S
R
ExternalCtrl
AND
OR
S
R
AND
AND
OR
StartByCBOpen
AND
AND
AND
AND
100ms
100ms
OR
OR
t
120ms
t
tCBClosedMin
AND
OR
AND
AND
OR
AND
AND
SETON
ON
OFF
initiate
START
CBREADY
CBCLOSED
READY
STARTHS
startThermal
inhibit
INHIBIT
start
count0
CBReady
cbClosed
IEC16000153 V1 EN-US
Figure 152: Simplified logic for Operation Off/On and starting
Mode selection
GUID-25A24DC8-80C8-4C42-A084-D25712049F06 v1
The auto reclosing mode is selected with the setting ARMode. As an alternative to
the setting, the mode can be selected by connecting an integer, for example from
function block B16I, to the MODEINT input. The six possible modes are described
in Table
176 below with their corresponding MODEINT integer value.
When a valid integer is connected to the input MODEINT the selected setting
ARMode will be invalid and the MODEINT input value will be used instead. The
selected mode is reported as an integer on the MODE output.
Please note that tripping mode of the IED is defined in Trip Logic function block
SMPPTRC. For example for two-phase faults either 2ph or 3ph tripping and
consequent auto reclosing can be selected
Section 12 1MRK 505 394-UEN A
Control
330 Line differential protection RED650 2.2 IEC
Technical manual