Name Type Default Description
BLKCLS_VLD BOOLEAN 0 Valid data on BLKCLS input
POSVAL INTEGER 0 Switch position, Pos.stVal
POSVAL_VLD BOOLEAN 0 Valid data on POSVAL input
OPCNT INTEGER -1 Operation counter
OPCNT_VLD BOOLEAN 0 Valid data on OPCNT input
BLK BOOLEAN 0 Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN 0 Valid data on BLK input
STSELD BOOLEAN 0 The controllable data is in the status "selected”
STSELD_VLD BOOLEAN 0 Valid data on STSELD input
OPRCVD BOOLEAN 0 Operate command for a controllable data object
received
OPRCVD_VLD BOOLEAN 0 Valid data on OPRCVD input
OPOK BOOLEAN 0 Operate command for a controllable data object
accepted
OPOK_VLD BOOLEAN 0 Valid data on OPOK input
EEHEALTH INTEGER -1 External equipment health
EEHEALTH_VLD BOOLEAN 0 Valid data on EEHEALTH input
OPCAP INTEGER -1 Operating capability
OPCAP_VLD BOOLEAN 0 Valid data on OPCAP input
COMMVALID BOOLEAN 0 Communication valid
XIN GROUP
SIGNAL
- Execution information from CSWI
PID-6712-OUTPUTSIGNALS v3
Table 202: XLNPROXY Output signals
Name
Type Description
XPOS GROUP SIGNAL Group connection to CSWI
SELECTED BOOLEAN Select conditions are fulfilled
OP_BLKD BOOLEAN Indication that the function is blocked for open
commands
CL_BLKD BOOLEAN Indication that the function is blocked for close
commands
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during
command
EEHEALTH INTEGER External equipment health. 1=No warning or
alarm, 2=Warning, 3=Alarm
OPCAP INTEGER Switch / breaker operating capability
1MRK 505 394-UEN A Section 12
Control
Line differential protection RED650 2.2 IEC 379
Technical manual