Name Values (Range) Unit Step Default Description
UL1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL2RepTyp Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Cyclic Reporting type
UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL3DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL3ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL3Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL3Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL3RepTyp Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Cyclic Reporting type
UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL3AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Table 364: VNMMXU Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
UL1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL3HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
Table continues on next page
1MRK 505 394-UEN A Section 15
Monitoring
Line differential protection RED650 2.2 IEC 515
Technical manual