Name Values (Range) Unit Step Default Description
UnderTrigLe03 0 - 200 % 1 50 Under trigger level for analog channel 3
in % of signal
OverTrigOp03 Off
On
- - Off Use over level trigger for analog channel
3 (on) or not (off)
OverTrigLe03 0 - 5000 % 1 200 Overtrigger level for analog channel 3 in
% of signal
NomValue04 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 4
UnderTrigOp04 Off
On
- - Off Use under level trigger for analog
channel 4 (on) or not (off)
UnderTrigLe04 0 - 200 % 1 50 Under trigger level for analog channel 4
in % of signal
OverTrigOp04 Off
On
- - Off Use over level trigger for analog channel
4 (on) or not (off)
OverTrigLe04 0 - 5000 % 1 200 Over trigger level for analog channel 4 in
% of signal
NomValue05 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 5
UnderTrigOp05 Off
On
- - Off Use under level trigger for analog
channel 5 (on) or not (off)
UnderTrigLe05 0 - 200 % 1 50 Under trigger level for analog channel 5
in % of signal
OverTrigOp05 Off
On
- - Off Use over level trigger for analog channel
5 (on) or not (off)
OverTrigLe05 0 - 5000 % 1 200 Over trigger level for analog channel 5 in
% of signal
NomValue06 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 6
UnderTrigOp06 Off
On
- - Off Use under level trigger for analog
channel 6 (on) or not (off)
UnderTrigLe06 0 - 200 % 1 50 Under trigger level for analog channel 6
in % of signal
OverTrigOp06 Off
On
- - Off Use over level trigger for analog channel
6 (on) or not (off)
OverTrigLe06 0 - 5000 % 1 200 Over trigger level for analog channel 6 in
% of signal
NomValue07 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 7
UnderTrigOp07 Off
On
- - Off Use under level trigger for analog
channel 7 (on) or not (off)
UnderTrigLe07 0 - 200 % 1 50 Under trigger level for analog channel 7
in % of signal
OverTrigOp07 Off
On
- - Off Use over level trigger for analog channel
7 (on) or not (off)
OverTrigLe07 0 - 5000 % 1 200 Over trigger level for analog channel 7 in
% of signal
NomValue08 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 8
UnderTrigOp08 Off
On
- - Off Use under level trigger for analog
channel 8 (on) or not (off)
UnderTrigLe08 0 - 200 % 1 50 Under trigger level for analog channel 8
in % of signal
Table continues on next page
1MRK 505 394-UEN A Section 15
Monitoring
Line differential protection RED650 2.2 IEC 565