Name Values (Range) Unit Step Default Description
PCM600Access Off
On
- - On PCM600 access
FTP Off
On
- - On FTP and FTPS access
MMS Off
On
- - On IEC61850-8-1 MMS
GOOSE Off
On
- - On IEC61850-8-1 GOOSE
DNP3 Off
On
- - On DNP3 slave
SNTPServer Off
On
- - On SNTP server
FSTAccess Off
On
- - On Field Service Tool access
C37.118TCP Off
On
- - On IEEE 1344 and C37.118 TCP server
C37.118UDP1 Off
On
- - On IEEE 1344 and C37.118 UDP stream
and the TCP control server
C37.118UDP2 Off
On
- - On IEEE 1344 and C37.118 UDP stream
and the TCP control server
C37.118UDP3 Off
On
- - On IEEE 1344 and C37.118 UDP stream
and the TCP control server
C37.118UDP4 Off
On
- - On IEEE 1344 and C37.118 UDP stream
and the TCP control server
C37.118UDP5 Off
On
- - On IEEE 1344 and C37.118 UDP stream
and the TCP control server
C37.118UDP6 Off
On
- - On IEEE 1344 and C37.118 UDP stream
and the TCP control server
DefaultGateway 0 - 18 IP
Address
1 0.0.0.0 Default gateway IP address
PID-6637-SETTINGS v3
Table 440: AP_FRONT Non group settings (basic)
Name
Values (Range) Unit Step Default Description
IPAddress 0 - 18 IP
Address
1 10.1.150.3 IP address of the access point
SubnetMask 0 - 18 IP
Address
1 255.255.255.0 Subnet mask of the access point
Description 1 - 18 - 1 FrontPort User editable access point description
[1-18 char]
PCM600Access Off
On
- - On PCM600 access
FTP Off
On
- - On FTP and FTPS access
MMS Off
On
- - On IEC61850-8-1 MMS
GOOSE Off
On
- - On IEC61850-8-1 GOOSE
Table continues on next page
Section 17 1MRK 505 394-UEN A
Ethernet
624 Line differential protection RED650 2.2 IEC
Technical manual