Name Function
block
SPA
address
Description
Update Block SXSWI16 3 I 472 SPA parameter for update block
command
Update Block SXSWI17 3 I 491 SPA parameter for update block
command
Update Block SXSWI18 3 I 510 SPA parameter for update block
command
Update Block SXSWI19 3 I 529 SPA parameter for update block
command
Update Block SXSWI20 3 I 548 SPA parameter for update block
command
Update Block SXSWI21 3 I 567 SPA parameter for update block
command
Update Block SXSWI22 3 I 586 SPA parameter for update block
command
Update Block SXSWI23 3 I 605 SPA parameter for update block
command
Update Block SXSWI24 3 I 624 SPA parameter for update block
command
Update Block SXSWI25 3 I 643 SPA parameter for update block
command
Update Block SXSWI26 3 I 662 SPA parameter for update block
command
Update Block SXSWI27 3 I 681 SPA parameter for update block
command
Update Block SXSWI28 3 I 700 SPA parameter for update block
command
Horizontal communication
M15083-86 v4
Network variables are used for communication between 500 and 650 series IEDs
The supported network variable type is SNVT_state (NV type 83). SNVT_state is
used to communicate the state of a set of 1 to 16 Boolean values.
Multiple command send function block (MULTICMDSND) is used to pack the
information to one value. This value is transmitted to the receiving node and
presented for the application by a multiple command receive function block
(MULTICMDRCV). With horizontal communication, the input BOUND on
MULTICMDSND must be set to 1. There are 10 MULTICMDSND and 60
MULTICMDRCV function blocks available. These function blocks are connected
using the LON network tool (LNT). The tool also defines the service and
addressing on LON.
This is an overview for configuring the network variables for the IEDs.
Configuration of LON network variables
M15083-92 v3
Configure the Network variables according to the specific application using the
LON network tool (LNT). The following is an example of how to configure
network variables concerning, for example, interlocking between two IEDs.
Section 18 1MRK 505 394-UEN A
Station communication
694 Line differential protection RED650 2.2 IEC
Technical manual