Autorecloser ON/OFF
Teleprotection ON/OFF
Protection ON/OFF
LED reset
Characteristics 1 - 4 (Setting groups)
File transfer (disturbance files)
Time synchronization
For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard
part 5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.
IEC 60870-5-103 vendor specific implementation
M11874-23 v4
The signal and setting tables specify the information types supported by the IEDs
with the communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in
the protection and control IED.
Be aware of that different cycle times for function blocks must be
considered to ensure correct time stamping.
Commands in control direction
M11874-27 v1
Commands in control direction, I103IEDCMD
M11874-29 v6
Command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Table 532: I103IEDCMD supported indications
INF
Description
19 LED Reset
23 Activate setting group 1
24 Activate setting group 2
25 Activate setting group 3
26 Activate setting group 4
Function commands in control direction, pre-defined I103CMD
M11874-53 v6
Function command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
1MRK 505 394-UEN A Section 18
Station communication
Line differential protection RED650 2.2 IEC 729
Technical manual