Table 537: I103SUPERV supported functions
INF Description TYP GI COT
32 Measurand supervision I 1 Y 1,7,9
33 Measurand supervision U 1 Y 1,7,9
37 I>>back-up operation 1 Y 1,7,9
38 VT fuse failure 1 Y 1,7,9
46 Group warning 1 Y 1,7,9
47 Group alarm 1 Y 1,7,9
Earth fault indications in monitor direction, I103EF
M11874-199 v8
Indication block for earth fault in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 538: I103EF supported indications
INF
Description
51 Earth fault forward
52 Earth fault reverse
Autorecloser indications in monitor direction, I103AR
M11874-363 v6
Indication block for autorecloser in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 539: I103AR supported indications
INF
Description
16 Autorecloser active
128 CB on by Autorecloser
130 Autorecloser blocked
Function status fault protection for IEC 60870-5-103, I103FLTPROT
GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signal.
Section 18 1MRK 505 394-UEN A