Table 542: I103MEASUSR supported indications
INF FUN GI TYP COT Description
*
1)
*
2)
No, polled
with CL2
*
3)
2,7 Meas1
* * No, polled
with CL2
* 2,7 Meas2
* * No, polled
with CL2
* 2,7 Meas3
* * No, polled
with CL2
* 2,7 Meas4
* * No, polled
with CL2
* 2,7 Meas5
* * No, polled
with CL2
* 2,7 Meas6
* * No, polled
with CL2
* 2,7 Meas7
* * No, polled
with CL2
* 2,7 Meas8
* * No, polled
with CL2
* 2,7 Meas9
1) * User defined information value (PARAM.3)
2) * User defined information value (PARAM.2)
3) 9 = Measurands II, Format = Measurand II (7.3.1.8 in IEC 60870-5-103:1997), semantics per IE is
defined by semantics of connected source.
<Number of information elements> is defined by index of first input not connected.
Example: Input1, Input2, and Input4 are connected, Input3 is not connected.
<Number of information elements> will be 3 (Input3 NOT connected) -1 = 2, that
is, only Input1 and Input2 will be transmitted.
Disturbance recordings
M11874-467 v7
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:
• I
L1
connected to channel 1 on disturbance function block A1RADR
• I
L2
connected to channel 2 on disturbance function block A1RADR
• I
L3
connected to channel 3 on disturbance function block A1RADR
• I
N
connected to channel 4 on disturbance function block A1RADR
• U
L1E
connected to channel 5 on disturbance function block A1RADR
• U
L2E
connected to channel 6 on disturbance function block A1RADR
• U
L3E
connected to channel 7 on disturbance function block A1RADR
• U
EN
connected to channel 8 on disturbance function block A1RADR
1MRK 505 394-UEN A Section 18
Station communication
Line differential protection RED650 2.2 IEC 735
Technical manual