Name Values (Range) Unit Step Default Description
TraAOnInpCh No Transf A
1
2
3
-
- No Transf A Power transformer A applied on input
channel X
RatVoltW1TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransA 0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
- - 0 [0 deg] Transf. A phase shift in multiples of 30
deg, 5 for 150 deg
TraBOnInpCh No Transf B
1
2
3
-
- No Transf B Power transformer B applied on input
channel X
RatVoltW1TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransB 0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
- - 0 [0 deg] Transf. B phase shift in multiples of 30
deg, 2 for 60 deg
PID-3560-SETTINGS v6
Table 39: LDLPSCH Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
TestModeSet Off
On
- - Off Test mode On/Off
ReleaseLocal Block all
Release local
- - Block all Release of local terminal for trip under
test mode
Section 6 1MRK 505 394-UEN A
Differential protection
92 Line differential protection RED650 2.2 IEC