Configure and Start the Kinetix 5500 Drive System Chapter 6
Menu Screens
The menu screens provide information about the drives, motors, diagnostics,
and the fault log. Parameters cannot be updated in the menu screens. Press one
of the menu buttons to access the menu.
You can use the soft menu items and navigation buttons to
view the information.
MAIN MENU
MOTOR INFO
MODULE INFO
Menu/Sub Menu
Selections
Attributes Description Example Values
Drive Info Catalog number 2198-Hxxx-ERSx
Firmware revision FW REV: 1.1.450167
Hardware revision HW REV: 1.1
Serial number SERIAL#: xxxxxxxxxxx
Motor Info Model number MODEL: VPL-B1306F
Serial number SERIAL#: xxxxxxxxxxx
Diagnostics>
Drive Diagnostics
Bus diagnostics BUS VOLT: 0.0V
BUS CUR: 0.0A
Converter diagnostics CONV UTIL: 0.7%
CONV TEMP: 31.7C
Inverter diagnostics INV UTIL: 0.0%
INV TEMP: 31.7C
Diagnostics>
Motor Diagnostics
Motor speed SPEED:0.0 RPM
Motor current MTR CUR:0.0A RMS
Motor utilization MTR UTIL:0.0%
Motor temperature MTR TEMP:0.00C
Diagnostics>
Encoder Diagnostics
Serial number SERIAL#xxxxxxxxxxx
Resolution RESOLUTION: 262144
Number of turns NO OF TURNS: 1
Encoder temperature ENC TEMP:33.7C
Supply voltage SUPP VOLT:11.3V
Link quality The link quality attribute indicates how noisy a communication link is and also indicates if there is a communication
link already established at the drive end. The LINK QUAL value must always be 100%. Persistent values below 100%
indicates a poor feedback ground connection.
LINK QUAL: 100.0%
Remote signal strength
indicator
Similar to Link Quality, RSSI reports the quality of link as seen at the motor end by the encoder. Maintain the RSSI value
between 80 and 100%. Persistent values below 80% indicates a poor feedback ground connection.
RSSI: 100.0%
Accumulated position
errors
This is an aggregated number of errors in the primary position feedback channel of DSL feedback. POS ERRORS: 1
Channel position errors This is an aggregated number of errors on a secondary communication channel of the DSL feedback. CHNL ERRORS: 5
Fault Log Fault text Fault code as listed in the Kinetix 5500 Fault Codes.xlsx file.
(1)
FLT S20 - CONV OVERLOAD FL
Fault details
The problem as reported in the Kinetix 5500 Fault Codes.xlsx file.
(1)
The converter thermal model indicates that the
temperature has exceeded the factory set capacity
rating of 110%.
Fault help
The Possible Solution as reported in the Kinetix 5500 Fault Codes.xlsx file.
(1)
• Reduce the number of drives in the same bus group
• Reduce duty-cycle of commanded motion
(1) See Access the Attachments on page 13 for information on accessing the Kinetix 5500 Fault Codes.xlsx file.