220 Rockwell Automation Publication 2198-UM001I-EN-P - May 2019
Appendix C Size Multi-axis Shared-bus Configurations
Shared AC/DC Configurations
In a shared AC/DC configuration, the first (leftmost) drive receives AC input
voltage. The shared-bus connection system extends the AC and DC bus to all
downstream drives:
All drives are configured in the project file as Shared AC/DC drives.
Drives must be of the same power rating (catalog number).
Shared AC/DC configurations support Bulletin 2198 capacitor
modules
Total available converter power is derated by 30%.
The maximum number of drives configured as Shared AC/DC is
described in Table 80
.
Table 80 - Shared AC/DC Panel Layout
Figure 108 - Typical Shared AC/DC Configuration
For an example shared AC/DC installation with additional details, refer to
Typical Shared AC/DC Installations
on page 19.
Drive Cat. No. Frame Size Drives Configured as Shared AC/DC, max
(1)
(1) For Bulletin 2198 capacitor module maximum values, refer to the Kinetix 5500 Capacitor Module Installation Instructions,
publication 2198-IN004
.
Number of Capacitor
Modules, max
2198-H003-ERSx
18
0
2198-H008-ERSx 1
2198-H015-ERSx
24 42198-H025-ERSx
2198-H040-ERSx
2198-H070-ERSx 32 4
Bonded Cabinet