EasyManua.ls Logo

Allen-Bradley Kinetix 5500 - Phase Loss Detection Current Example

Allen-Bradley Kinetix 5500
272 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2198-UM001I-EN-P - May 2019 259
Motor Control Feature Support Appendix D
Phase Loss Detection Current Example
In this example, a 2198-H025-ERSx servo drive is paired with a
VPL-B1003T-C motor with 6.77 A rms rated current. Use the phase-loss
detection equation and table to calculate the initial minimum torque-proving
current as a percentage of motor rated current. Depending on the unique
characteristics of your application, the required torque-proving current value
can be larger than the initial recommended value.
Figure 136 - Phase-loss Detection Equation
Table 96 - Recommended Phase-loss Detection Current
Rating From Table
x 100% =
Motor Rated Current
0.5746 A
6.77 A
x 100% =
8.49%
Drive Cat. No.
Phase-loss Detection Current, min
A, rms
2198-H003-ERSx 0.2514
2198-H008-ERSx 0.6285
2198-H015-ERSx 1.257
2198-H025-ERSx 2.011
2198-H040-ERSx 3.268
2198-H070-ERSx 5.782

Table of Contents

Other manuals for Allen-Bradley Kinetix 5500

Related product manuals