Fault List & Troubleshooting 461
© 2020, ATEÏS. All rights reserved.
see the picture as below.
o EVAC Input Error (SHORT)
"EVAC Input Error" message will be displayed on the touch screen of IDA8C:
o A text message will be displayed at the [Machine Fault Record] window in Ateis Studio,
see the picture as below.
A buzzing sound will be outputted to the monitoring speaker on the front panel of the IDA8C.
Fault Handling : Evacuation Intput Error
7.1.8 Local Ateis-Net Broken
The Local Ateis Net is broken, this problem may come from the wire connection between devices
on the Ateis Net or the net card on the device.
Indication:
LED Indicator: When this error is detected, the following LED will light up:
o G. Fault LED on the front panel of the IDA8C/S.
Log:
o "Local AteisNet Broken" message displays on the touch screen of IDA8C.
o A text message displays at the [Machine Fault Record] window in Ateis Studio, see the
picture as below.