Fault List & Troubleshooting 459
© 2020, ATEÏS. All rights reserved.
7.1.6 Amplifier Line Leakage Error
An electricity leakage between the IDA8C/S and the speaker is detected. The measurement of
speaker lines has short-circuit fault due to the + speaker line is connected to ground wire, and - is
connected to ground wire.
Indication:
LED Indicator:
When this error is detected, the following LEDs will light up:
o G. Fault LED on the front panel of the IDA8C/S.
o Zone Fault LEDs on the front panel of the IDA8C/S.
Log:
o The text messages will be displayed on the touch screen of the IDA8C as follows:
"AMP Line Leakage Error".