8 Parameter detail setup
© Copyright Reserved Autonics Co., Ltd. 115
8.6.8 Log Speed (Save period)
Designate the save period of measured data by universal input card (KRN-UI2) to system
memory. The recorded data on recording paper is also recorded by save period.
For example, 3 sec save period records every 3 sec data, but it does not record during 3 sec of
data which are changed.
Setting range: 0 to 3600
Factory default: None (0s)
If save period is set longer, the relation between graph data and alarm ON data is lower because
of the occuring alarm record in the middle of save period during recording.
When setting as ‘None (0s)’ for Log Speed(save period), recording operates normally but the
data does not saved at inner/external memory. If no recording paper ( P.E N D ) alarm occurs, there
is no designated data and backup data is not recorded.
8.6.9 Backlight (LCD backlight brightness)
Designate LCD backlight brightness as 4 levels.
Setting range: OFF ↔ Min ↔ Standard ↔ Max
Factory default: Standard
8.6.10 Backlight On/Off (LCD backlight ON method)
Designate LCD backlight ON method.
If you set as ‘Always’, it maintins ON status, as ‘Temp’, it maintains only for 30 sec when key is
input.
Setting range: Always ↔ Tem p
Factory default: Tem p