8 Parameter detail setup     
74    © Copyright Reserved Autonics Co., Ltd. 
8.2.3  Alarm□  Type(Alarm□  operation mode) 
 
Designate alarm operation when alarm ON.   
You can set up to 4 operations by each channel and alarm operations are as below.   
1 
No alarm 
-  -  - 
2 
Absolute 
value 
upper limit 
alarm 
PV.Hi 
(▲) 
Alarm set value: 90℃   
If display value is same or 
higher than alarm set value, 
alarm output turns ON. 
3 
Absolute 
value 
lower limit 
alarm 
PV.Lo 
(▼) 
Alarm set value: 90℃ 
If display value is same or 
lower than alarm set value, 
alarm output turns ON. 
4 
Deviation 
upper limit 
alarm 
DV.Hi 
(△) 
Alarm set value:   
-10℃ 
 
Alarm set value: 
10℃ 
 
If the deviation between 
display value and the 
display value of reference 
channel is same or higher 
than alarm set value, alarm 
output turns ON. 
5 
Deviation 
lower limit 
alarm 
DV.Lo 
(▽) 
Alarm set value: 
10℃ 
 
 
Alarm set value: 
-10℃ 
 
 
If the deviation between 
display value and the 
display value of reference 
channel is same or lower 
than alarm set value, alarm 
output turns ON. 
6 
Input 
break 
alarm 
SBA 
(S) 
In case input is not connected, or input cable is break during controlling, 
alarm output turns ON. You can check whether input cable is break by 
external contact of alarm output using buzzer or other devices.
 
7 
No 
recording 
paper 
alarm 
P.END 
(P) 
In case of no recording paper during recording, record operation stops 
and this alarm output turns ON. (Measuring value is saved at system 
memory automatically.)   
Alarm is automatically cleared when recording paper is replaced (in 
case of general alarm). P.END BACKUP PRINT window is activated 
and it is available to output backup data.