8 Parameter detail setup
© Copyright Reserved Autonics Co., Ltd. 63
8.1.12 Special Function (Special function)
It dispalys the applied measuring value of the set special function.
Depending on Input Type(Input specification), appliable special function is different.
Setting range
When input type(input specification) is
temperature sensor (thermocouple, RTD): None ↔ Difference
analog (voltage, current): Linear ↔ Root ↔ Squre ↔ Two Unit (Two Unit is displayed
when Input Type (input specification) is set as 0-20mA, 4-20mA.)
Factory default: None
Below graph’s patterns are liner, root, square for analog input.
Lower limit input value: -5V, Upper limit input value: +5V, Lower limit scale: -1000, Upper limit
scale: 1000