8 Parameter detail setup
80 © Copyright Reserved Autonics Co., Ltd.
8.2.8 Alarm ON/OFF Delay(Alarm ON/OFF output delay time)
Set delay time (unit: sec.) to prevent alarm malfunction by wrong input from external disturbance
and noise.
Item
Description
Alarm On Delay
Even after standby the set time when alarm ON condition (alarm ON
channel flashes on screen), if it is still alarm condition, alarm output turns
ON. (Alarm ON channel flashes on screen).
Alarm OFF Delay
Even after standby the set time when alarm reset condition (alarm ON
channel display is hold), if it is still alarm reset condition, alarm output turns
OFF. (Alarm ON channel resets the display.)
Setting range: 0 to 3600
Factory default: 0s