8 Parameter detail setup
72 © Copyright Reserved Autonics Co., Ltd.
8.2 ALARM SETUP (Alarm setting)
You can set alarm output specification such as alarm operation mode and alarm option by input
channel, alarm ON/OFF delay, alarm output relay, relay contact, etc.
Move to ALARM SETUP with , keys, press key to enter ALARM SETUP.
Parameter list
Parameter Setting range Unit
Factory
default
Select UI Card (Select universal card input)
CH-SUI-
-
Automaticall
y set
Alarm Set Copy (Copy alarm parameter)
No Select/ CH-SUI-
- CH Select
Alarm Type(Alarm operation mode)
1
OFF PV. Hi PV. Lo DV.Hi
DV. Lo SBA P. E N D
-
Alarm1
Type: PV.Hi
Alarm2
Type to
Alarm4
Type: None
Alarm Ref Channel(Alarm reference
channel)
None / CH-SUI-
- -
Alarm Option(Alarm option)
1
None Latch StBy La+St
- None
Alarm Value(Alarm set value)
1
F.S. of INPUT TYPE by channel Digit
Alarm1
Value:
1350.0
Alarm2
Value to
Alarm4
Value: -
Alarm Hysteresis(Alarm hysteresis)
1
F.S. of INPUT TYPE by channel Digit 0.0
Alarm ON/OFF Delay(Alarm ON/OFF
output delay time)
1
0 to 3600 sec 0s
Alarm Alarm No(Alarm output alarm
number)
1
None / SAO-
- None
Select Alarm Card(Select alarm output
card)
- -
Automaticall
y set
Alarm- Status(Relay and transistor
output method)
1
N.O.
N.C.
When connecting Relay type KRN-AR4
(alarm output card), AL1 to AL4 are
activated.
When connecting transistor type KRN-AT6
(alarm output card), AL1 to AL6 are
activated.
N.O.
N.O.N.C.
N.O.
N.O.N.C.
N.O.
N.O.N.C.
N.O.
N.O.N.C.
N.O.
N.O.N.C.
N.O.