Displays error messages on screen and print data when error occurs.
Error message
Description
HHHH
In case Input Type is temperature sensor(thermocouple, RTD), if input value is
higher than upper limit range, this error message flashes. If input value is within
upper limit range, it is removed automatically.
In case Input Type is analog(current, voltage), if input value is higher than over
10% of upper limit input range, this error message flashes. If input value is within
10% of upper limit input range, it is removed automatically.
Prints HH.
LLLL
In case Input Type is temperature sensor(thermocouple, RTD), if input value is
lower than lower limit range, this error message flashes. If input value is within
lower limit range, it is removed automatically.
In case Input Type is analog(current, voltage), if input value is lower than over
10% of lower limit input range, this error message flashes. If input value is within
10% of lower limit input range, it is removed automatically.
Prints LL.
_H
In case Input Type is analog(current, voltage), if input value is higher than below
10% of upper limit input range, “_H” is displayed with current value to notify that
current value is higher than upper limit input range.
E.g.) When upper limit input range is 100 and current value is 102, it displays as
102_H.
_L
In case Input Type is analog(current, voltage), if input value is lower than below
10% of lower limit input range, “_L” is displayed with current value to notify that
current value is lower than lower limit input range.
E.g.) When lower limit input range is 0 and current value is -1, it displays as -
1_L.
BURN
If input is break, this error message flashes. When input is connected, it is
removed automatically.
Prints BH(display value by break is High) or BL (display value by break is Low).
Refer to 8.1.19 Burnout Action (Display setting for break).
NONE
If universal input card is not connected, this error message flashes.
ERR
When there is parameter setting error, card recognition error, etc, this error
message flashes twice and KRN100 returns to previous screen.
Inner Memory
Access
As above screen, if excess error message for inner system memory Read/Write
occurs frequently, please contact our service center.