8 Parameter detail setup
92 © Copyright Reserved Autonics Co., Ltd.
8.4.7 Response Wait Time (Communication response wait time)
To prevent possible error due to communicating with low speed Master (PC, PLC, etc), set
communication response wait time.
If you set too short communication response wait time, communication error may occur in
Master.
Setting range: 5 to 99 (unit: ms)
Factory default: 20ms
8.4.8 Protocol (Communication protocol)
It supports Modbus RTU(Remote Terminal Uint) as communication protocol.
(Data Length: 8bit, Data interval: 24bits or less,Error Detection: CRC-16)
Setting range: Modbus RTU
Factory default: Modbus RTU
8.4.9 RS485 Com Write (RS485 communication write)
Set whether changing the set value of KRN100 parameter by RS485 communication.
To read the set value of each parameter is available regardless of the communication write
enable/disable setting.
Setting range : Enable ↔ Disable
Factory default : Enable