Using the display panel Azbil Corporation
4-62 Model MGG10C/14C - MagneW FLEX+/PLUS+ Converter
Coe󰀩cient of compensation
This function changes the Coecient, which multiplies the output ow rate in the
main display.
Step
Screen
Procedure
(English) (Japanese)
1
COEFFICIENT
1.0000
&
1.0000
&
Enter ADVANCED MODE (see
page 4-23).
Use the
or key to cycle
through the screens until the
COEFFICIENT screen appears.
2
COEFFICIENT
1.0000
&
1.0000
&
Touch the key until the cursor
is at the value to be changed.
Default setting: 1.0000
Setting Range: 0.1000 to 9.9999
3
COEFFICIENT
1.0050
&
1.0050
&
Touch the or key to change
the value.
4
COEFFICIENT
1.0050
&
1.0050
&
Touch the key until the cursor
is back at the mode indicator.
5
Touch the MODE key and hold
for three seconds to return to
MEASUREMENT MODE to save
the new value.
CAUTION
You must return to
MEASURING MODE within
two minutes to save this new
value before the system resets
it to the previously saved
value.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Azbil MagneW FLEX+/PLUS+ MGG10C and is the answer not in the manual?

Azbil MagneW FLEX+/PLUS+ MGG10C Specifications

General IconGeneral
BrandAzbil
ModelMagneW FLEX+/PLUS+ MGG10C
CategoryMedia Converter
LanguageEnglish

Related product manuals