Using the display panel  Azbil Corporation
4-32  Model MGG10C/14C - MagneW FLEX+/PLUS+ Converter
Normal direction, external switching dual range
The range is switched via an external switching command to the contact input.
Also, the wide/narrow range distinction contact output (status signal) can be sent out 
using the same timing.
Analog output
j  When AUTO is selected for an analog output
  Range No.1 4 to 20 mA DC
  Range No.2 4 to 20 mA DC
k  When WIDE is selected for an analog output
   4 to 20 mA DC is output according to either range No.1 or range No.2 whichever 
has the wider range.
When there is a pulse output
  The pulse weight is the same for both ranges No.1 and No.2.
Contact input
  Range switching command contact input
  Range No.1: Close
  Range No.2: Open
Contact output (select functions as required.)
  Range switching distinction status signal
  The contact output status at shipment is as follows.
  Range No.1: Closed
  Range No.2: Open
Reverse setting is also possible.