Using the display panel Azbil Corporation
4-32 Model MGG10C/14C - MagneW FLEX+/PLUS+ Converter
Normal direction, external switching dual range
The range is switched via an external switching command to the contact input.
Also, the wide/narrow range distinction contact output (status signal) can be sent out
using the same timing.
Analog output
j When AUTO is selected for an analog output
Range No.1 4 to 20 mA DC
Range No.2 4 to 20 mA DC
k When WIDE is selected for an analog output
4 to 20 mA DC is output according to either range No.1 or range No.2 whichever
has the wider range.
When there is a pulse output
The pulse weight is the same for both ranges No.1 and No.2.
Contact input
Range switching command contact input
Range No.1: Close
Range No.2: Open
Contact output (select functions as required.)
Range switching distinction status signal
The contact output status at shipment is as follows.
Range No.1: Closed
Range No.2: Open
Reverse setting is also possible.