Azbil Corporation  Installation
Model MGG10C/14C - MagneW FLEX+/PLUS+ Converter  2-15
Wiring cable
Selecting the cable
The recommended wiring cable is a 600V vinyl sheath electrical wire CVV (JIS C 
3401) with a conductor section of 2 mm
2
(0.0031 inch
2
), or a twisted cable with an 
equivalent or higher capacity.
Shielded wire is recommended for wiring at locations subject to electromagnetic 
noise interference.
Select a sheath material suitable for the cable installation environment (consider 
ambient temperature, corrosive gas, corrosive uid, etc.)
Run the cable into the terminal block through the conduit connection (G1/2 internal 
thread, CM20 external thread, Pg13.5 or 1/2NPT internal thread).
An outer diameter of 
f
11(0.433 inch) is optimum. (The applicable range of cable 
outer diameters is 
f
10(0.394 inch) - 
f
12(0.4724 inch).)
A crimp terminal (M4 screw) with an insulation sleeve is recommended for the 
terminal connections.
The maximum length of the wiring cable is 1500 m(4921 ft). However, the maximum 
length between converter and detector is 300 m(984 ft).
Wiring the cable
When wiring the cable between this product and the control equipment, the following 
precautions must be observed.
~ Note
• Run the wiring away from equipment that may generate noise, such as high-
capacity transformers, motors, or power supplies. DO NOT install the cable in the 
same tray or duct as other power cables. Output errors may result.
• For water proong and damage prevention of the wire, we recommend cabling 
work using conduits and ducts. Use a water proof cable gland.