Using the display panel Azbil Corporation
4-56 Model MGG10C/14C - MagneW FLEX+/PLUS+ Converter
Damping time constant
The damping time constant removes minute uctuations when transmitting the
measured ow rate to the control equipment. Check the amplitude of uctuation in
ow output and set the damping time constant to an appropriate value. The new value
becomes eective as soon as it is entered
Default setting
3.0 second.
Setting range
0.1 to 199.9 seconds.
(0.0 to 199.9 seconds for “Fast Response Option for Short Run Batch Process.”)
Step
Screen
Procedure
(English) (Japanese)
7
MODE ENTER
Enter the ADVANCED mode.
(See page 4-23).
8
DAMPING
&
&
Use the Touch or key to
cycle through the screens until
the damping screen appears.
9
DAMPING
003.0s
& &
Touch the key until the
cursor is at the value to be
changed. (in the example, the
key is touched three times.)
10
DAMPING
010.0s
&
&
Use or key to change
the numeric value. Touch and
holding either key quickly
increments or decrements the
values.
11
DAMPING
010.0s
&
&
Touch the key until the
cursor is back at the mode
indicator. Touch the MODE
key and hold for three seconds
to return to MEASUREMENT
MODE to save the Damping
Time Value.