Azbil Corporation  Maintenance and Troubleshooting
Model MGG10C/14C - MagneW FLEX+/PLUS+ Converter  5-5
Contact input/output loop check
By switching contact input terminal ON/OFF, contact input terminal status can be 
checked through the LCD.
By switching contact output terminal ON/OFF, contact output loop can be checked.
Display varies according to the selection of contact input and output.
Default setting
Display the existing status
Setting range
“CLOSE”, “OPEN”
<Contact input and contact output>
Step
Screen
Procedure
(English) (Japanese)
1
>
T. IN   
PE
Enter MAINTENANCE MODE 
(see page 4-24). Use the 
 or 
 key to cycle through screen 
until “OUTPUT CHECK” 
screen appears. Touch the 
 
key once to move the cursor 
to “OFF”. Touch the 
 key to 
switch the OFF screen to ON 
screen. Touch the 
 key twice 
to move to “OUTPUT CHECK 
ST. IN/OUT” screen.
2
>
T. IN   
PE
>
Touch the   key to move the 
cursor at the status (OPEN/
CLOSE).
3
>
T. IN   CL
E  
>
4 - 20    100.0 
Use the   key to select the 
desired output status (OPEN/
CLOSE).
4
>
T. IN   CL
E  
>
4 - 20    100.0 
For the contact input, the display 
indicates current contact input 
status (OPEN/CLOSE).