Table 1: Quick Start Parameters for Vector Plus and Vector VII Applications (cont'd.)
The default auto-restart time, in
minutes, for all system faults. Note
that the restart time for any trigger
(fault detection mechanism) can
be customized from the Trigger
Info screen.
Restart delay after a power loss
when running. The default value
is the global restart time. When
the value is changed, the user
can specify whether the new
value applies only to the PwrFail
SysStop trigger or if the global
restart time should be changed.
PwrFail SysStop Restart Delay
Restart delay after a power loss
when running. The default value
is the global restart time. When
the value is changed, the user
can specify whether the new
value applies only to the PwrFail
SysStop trigger or if the global
restart time should be changed.
Set to No-Load Test if you plan to
run no-load tests.
Adjust the setpoint as desired.
Note that changes to the setpoint
are applied immediately.
When set to true, the drive will
only start when the Start button
on the keypad is pressed. When
set to false, the drive will also start
on automatic restarts and SCADA
start commands. By default,
ManualStartOnly is set to true any
time a configuration or a template
is loaded to prevent unexpected
startup.