276
890053-00-02
Time Event Module Function Settings
The functions to be performed in the Time Event for T-Events 18 can be set with the 30 functions listed in
AP3-73~AP3-87. There are 8 Time event modules in the Time Event. The parameters for T-Events 18 are
used to set the connections to each module for the Time Period and the Exception Date. The parameters
for T-Events 18 are used to specify the operation on particular days.
Example of the Time Event operations
If the Time events are set as the parameters below, the inverter operates as illustrated.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
06
Command
Source
Cmd Ref Src
5: Time Event
09
-
07
Frequency
command
source
Freq Ref Src
0: KeyPad
011
-
AP3
11
Time Period 1
Start time
Period1 StartT
10: 00
00: 0024: 00
Min
12
Time Period 1
End time
Period1 Stop T
20: 00
00: 0024: 00
Min
13
Time Period 1
Day of the
week
Period1 Day
0110000
0000000
1111111
14
Time Period 2
Start time
Period2 StartT
12: 00
00: 0024: 00
Min
15
Time Period 2
End time
Period2 Stop T
17: 00
00: 0024: 00
Min
16
Time Period 2
Day of the
week
Period2 Day
00100000
0000000
1111111
-
70
Time Event
configuration
Time Event En
1: YES
0
No
-
1
Yes
72
Time Event 1
connection
configuration
T-Event1Period
00000000000
000000000000
111111111111
73
Time Event 1
functions
T-Event1Define
1: Fx
0
None
1
Fx
2
Rx
3
Speed-L
4
Speed-M
5
Speed-H
7
Xcel-L
8
Xcel-M
9
Xcel-H
10
Xcel Stop
11
Run Enable
12
2nd Source
13
Exchange
14
Analog Hold