Cisco IE 3000 Switch Command Reference
OL-13019-01
Chapter 2 IE 3000 Switch Cisco IOS Commands
alarm facility temperature
alarm facility temperature
Use the alarm facility temperature global configuration command to configure a primary temperature
monitoring alarm or to configure a secondary temperature alarm threshold with a lower maximum
temperature threshold. Use the no form of this command to delete the temperature monitoring alarm
configuration or to disable the secondary temperature alarm.
alarm facility temperature {primary {high | low | notifies | relay {major | minor} | syslog} |
secondary {high | low | notifies | relay {major | minor} | syslog}}
no alarm facility temperature {primary {high | low | notifies | relay {major | minor} | syslog} |
secondary {high | low | notifies | relay {major | minor} | syslog}}
Syntax Description
Defaults The primary temperature alarm is enabled for a –4 to 203ºF (–20 to 95
o
C) range and cannot be disabled.
It is associated with a major relay. The secondary temperature alarm is disabled by default.
Command Modes Global configuration
Command History
Usage Guidelines The primary temperature alarm is automatically enabled. It cannot be disabled, but you can configure
alarm options.
You can modify the primary temperature alarm range by using the high and low keywords.
You can use the secondary temperature alarm to trigger a high temperature alarm that is lower than the
maximum primary temperature threshold, which is 203
o
F
(95
o
C). You can configure the temperature
threshold and alarm options.
Before you use the notifies keyword to send alarm traps to an SNMP host, you need to set up an SNMP
server by using the snmp-server enable traps global configuration command.
high Set the high temperature threshold for the primary or secondary temperature
alarm. The range is –238 to 572ºF (–150 to 300ºC).
low Set the low temperature threshold for the primary or secondary temperature
alarm. The range is –328 to 482ºF (–200 to 250ºC).
notifies Send primary or secondary temperature alarm traps to an SNMP server.
relay major Send the primary or secondary temperature alarm to the major relay circuitry.
relay minor Send the primary or secondary temperature alarm to the minor relay circuitry.
syslog Send primary or secondary temperature alarm traps to a syslog server.
Release Modification
12.2(44)EX1 This command was introduced.