7.7.64  AIN9 Level 1    [ ] 
Warning limit level for AIN9 
Step:     1  
Range:   0 - 10000  
Default:   20 
7.7.65  AIN9 Level 2    [ ] 
Shutdown limit level for AIN9 
Step:     1 
Range:   0 - 10000 
Default:   10 
7.7.66  AIN9 Del     [s] 
Delay for Wrn/Sd AIN9 alarm. 
Step:     1s 
Range:   0 - 3600s 
Default:   10s 
NOTE: 
Analog input 9 is configurable with basic two levels protection and it is voltage type of input with range 
0-10V. 
7.7.67  NextServTime   [h] 
Counting down when engine is running.  Service time alarm appears if reaches zero. By setting the 
value of 65535h the count down is disabled. 
Step:     1h 
Range:   0 – 65535h 
Default:   10 000 
NOTE: 
Set the NextServTime = 65535h to disable count down. The setpoint stays constant,  but Statistics 
value (visible in LiteEdit) displays #### invalid value. 
 
7.7.68  GearBoxRatio   [RPM] 
There  are  two  new  protections  related  to  RPM-BI3  where  functions  Engine  protect:  RPMdiff  Sd, 
RPMdiff Wrn limits depends on setting of GearBoxRatio: 
  Separate RPM-BI3 underspeed Wrn and Sd protection when Engine protect: GearBoxRatio 
= 0.0 
  Difference check between RPM and RPM3 with calculation of gear-box ratio, when Engine 
protect: GearBoxRatio > 0.0. Protection is active when engine is Ready to load. 
 
Step:     0.1RPM 
Range:   0.0 - 5.0RPM